Improving the Fault Tolerance of GFU Air
Cooler Control Systems: Transition
from a Ring Topology to Isolated Segments |
Dyma I.S., Shevlyagina S.A.
This article examines the low fault tolerance of air-cooled unit (ACU) control systems at gas fractionation units (GFUs), caused by the
use of a serial ring topology. The causes of cluster failures of variable-frequency drives (VFDs) during single network equipment failures
are analyzed. These failures lead to temperature disturbances during propane fraction condensation and pressure increases in the column
equipment. A technical solution is proposed based on the transition to a star topology by implementing fi eld switches in each control cabinet. This approach ensures fault localization and eliminates the impact of a single port failure on the operation of the entire fan group.
Additionally, the study substantiates the watchdog timer settings and drive behavior strategies in the event of communication loss, including
fail-safe mode. This, combined with the proposed topological upgrade, ensures process continuity in the presence of industrial interference.
Keywords: gas fractionation unit, air cooler, variable-frequency drive, network topology, fault tolerance.
DOI: 10.25791/asu.6.2026.1664
Pp. 13-18. |
|
|
|
Last news:
Выставки по автоматизации и электронике «ПТА-Урал 2018» и «Электроника-Урал 2018» состоятся в Екатеринбурге Открыта электронная регистрация на выставку Дефектоскопия / NDT St. Petersburg Открыта регистрация на 9-ю Международную научно-практическую конференцию «Строительство и ремонт скважин — 2018» ExpoElectronica и ElectronTechExpo 2018: рост площади экспозиции на 19% и новые формы контент-программы Тематика и состав экспозиции РЭП на выставке "ChipEXPO - 2018" |